DC Current sensor 0-5A i/p 0-10V o/p

This current sensor is specifically designed to measure current (non-contact sensing) in application of relatively low current but where interrupting the circuit is not an option. In is capable of detecting a 5mA change (0-5A i/p mode).
Ideal device for Level Crossing Monitor installations.”
- Input Current range
- 0-5A DC or 0-50A DC (Factory set)
- Input Absolute max. Rating
- 60A DC
- Input Connection
- Wire Feed trough (no connection required)
- Output Current range
- 0-5V DC or 0-10V DC (Factory set)
- Output Connection
- Front Panel Screw Terminal
- Accuracy Of the full range
- 0.25%
- Linearity Of the full range
- 0.25%
- Resolution On the full range
- 0.1% of input range
- Response From 10% to 90%
- 10ms
- Flow indication of the current
- Green Led ON for I >1%
- Red LED and Voltage free contact
- Full span alarm user settable via front face adjustment.
- Power Supply Absolute Rating
- 9-36V DC
- Power Supply Reverse polarity
- Fully protected without fuse
- Supply Current Maximum @ 9V
- 300mA
- Supply Current Maximum @ 36V
- 83mA
- Ambient Temperature
- -10 to 55 oC
- Temperature Coefficient
- +/-1 % of range maximum
- Storage Temperature
- -40 to 85 oC
- WEIGHT
- 103g
- SIZE
- Overall. 85 x 80 x 25mm